Defining Alarm Thresholds for Battery Voltage Sensors

To configure SNMP chassis alarm thresholds for battery voltage sensors:

  1. Set the editing level for the CLI to expert.
    user@host> set cli level expert
  2. From configuration mode, access the configuration statement that defines the thresholds for battery voltage sensors.
    [edit]user@host# edit snmp monitor chassis-alarm battery-voltage
  3. (Optional) Specify the lower threshold for the minor alarm. For example:
    [edit snmp monitor chassis-alarm battery-voltage]user@host# set below-minor 3024
  4. (Optional) Specify the lower threshold for the major alarm. For example:
    [edit snmp monitor chassis-alarm battery-voltage]user@host# set below-major 3008
  5. (Optional) Specify the lower threshold for the critical alarm. For example:
    [edit snmp monitor chassis-alarm battery-voltage]user@host# set below-critical 2992
  6. (Optional) Specify the upper threshold for the minor alarm. For example:
    [edit snmp monitor chassis-alarm battery-voltage]user@host# set over-minor 3744
  7. (Optional) Specify the upper threshold for the major alarm. For example:
    [edit snmp monitor chassis-alarm battery-voltage]user@host# set over-major 3760
  8. (Optional) Specify the upper threshold for the critical alarm. For example:
    [edit snmp monitor chassis-alarm battery-voltage]user@host# set over-critical 3776