SRX3400 Services Gateway AC Power Cord Specifications
Each AC power supply has a single AC appliance inlet located on the power supply that requires a dedicated AC power feed and a dedicated 15 A (250 VAC) circuit breaker. Most sites distribute power through a main conduit that leads to frame-mounted power distribution panels, one of which can be located at the top of the rack that houses the services gateway. An AC power cord connects each power supply to the power distribution panel.
The services gateway is not shipped with AC power cords, you must order them separately using the model number shown in Table 1. The services gateway uses detachable AC power cords with C19 appliance couplers at the socket end as described by International Electrotechnical Commission (IEC) standard 60320. The plug end of the power cord fits into the power source receptacle that is standard for your geographical location.
Table 1 provides specifications and Figure 1 depicts the plug on the AC power cord available for each country or region.
Table 1: AC Power Cord Specifications
Country | Model Number | Electrical Specification | Plug Type |
---|---|---|---|
Australia/New Zealand | CBL-M-PWR-RA-AU | 240 VAC, 50 Hz AC | SAA/3/15 |
China | CBL-M-PWR-RA-CH | 220 VAC, 50 Hz AC | CH2-16P |
Continental Europe (except Denmark, Italy, Switzerland, and United Kingdom) | CBL-M-PWR-RA-EU | 220 or 230 VAC, 50 Hz AC | CEE 7/7 |
Italy | CBL-M-PWR-RA-IT | 230 VAC, 50 Hz AC | CEI 23-16/VII |
Japan | CBL-PWR-RA-JP15 | 125 VAC, 50 or 60 Hz AC | JIS 8303 |
CBL-M-PWR-RA-JP | 220 VAC, 50 or 60 Hz AC | NEMA L6-20P | |
North America | CBL-PWR-RA-US15 | 125 VAC, 60 Hz AC | NEMA 5-15P |
CBL-PWR-RA-TWLK-US15 | 125 VAC, 60 Hz AC | NEMA L5-15P | |
CBL-M-PWR-RA-US | 250 VAC, 60 Hz AC | NEMA 6-20 | |
CBL-M-PWR-RA-TWLK-US | 250 VAC, 60 Hz AC | NEMA L6-20P | |
United Kingdom | CBL-M-PWR-RA-UK | 240 VAC, 50 Hz AC | BS89/13 |

The AC power cord for the services gateway is intended for use with the services gateway only and not for any other use.
In North America, AC power cords must not exceed 4.5 m (approximately 14.75 ft) in length, to comply with National Electrical Code (NEC) Sections 400-8 (NFPA 75, 5-2.2) and 210-52, and Canadian Electrical Code (CEC) Section 4-010(3). The cords listed in Table 1 are in compliance.
For information about the AC power supply, including a description of components, see SRX3400 Services Gateway AC Power Supply Overview. For instructions on connecting the power cord during initial installation, see Connecting the SRX3400 Services Gateway to an AC Power Source. For instructions on replacing the AC power cables, see Replacing AC Power Supply Cables on the SRX3400 Services Gateway.