MX2000 High-Voltage Universal PDM (MX2K-PDM-HV) Power Cord Specifications

 

Table 1 provides specifications and plug standards for the AC (20-input) power cord applicable to the universal (HVAC/HVDC) PDMs.

Table 1: 20-A Cabling Options

Spare Juniper Model Number

Locale

Cord Set Rating

Connector

CBL-JNP-SG4-C20

North America

AC Power Cord

20 A, 250 VAC

C20 to Anderson 3-5958p4

Table 2 provides specifications and connectors on the 30-A power cord provided for each country or region applicable to the universal (HVAC/HVDC) PDMs.

Table 2: 30-A Cabling Options

Spare Juniper Model Number

Locale

Cord Set Rating

Connector

CBL-PWR2-BARE

See Figure 1.

North America

HVAC/HVDC power cord

30 A, 400 VAC

Anderson/straight to bare wire

CBL-PWR-SG4

North America

HVAC/HVDC power cord

30-A, 400 VAC

SAF-D-GRID 400 right-angle (LH)

CBL-PWR2-L6-30P

See Figure 2.

North America

AC Power Cord

30 A, 400 VAC

Anderson/straight to L6-30P

CBL-PWR2-332P6W-RA

Continental Europe

AC power cord

30-A 250 VAC

Anderson/right-angle to IEC 332P6

CBL-PWR2-332P6W

Continental Europe

AC power cord

30-A 250 VAC

Anderson/right-angle to IEC 332P6

CBL-PWR-SG4-RA

USA

HVAC/HVDC power cord

30-A, 400 VAC

SAF-D-GRID 400 right-angle (LH)

CBL-PWR2-L6-30P-RA

North America

AC power cord

30 A, 250 VAC

Anderson/right-angle to L6-30P

CBL-PWR2-330P6W-RA Figure 3.

Continental Europe

AC power cord

30 A, 250 VAC

Anderson/right-angle to IEC 330P6

CBL-PWR2-330P6W

North America

AC power cord

30 A, 250 VAC

Anderson/right-angle to IEC 330P6

For the HVAC/HVDC power cord one end of the cable has an SAF-D-Grid 400 connector, the other end of the cable is bare wire. See Figure 1 and Table 2. These cables are separately orderable and are not shipped automatically with the MX2K-PDM-HV orders. An example of the bare wire cable and connector is shown in Figure 1.

For connection to AC systems, Juniper provides a cable with either a NEMA 30-A connector (Figure 2).

Figure 1: Bare Cable with Anderson Connector
 Bare Cable with Anderson Connector
  1
Black wire–Positive (+)
  3
White wire–Negative
  2
Green wire-Ground
 
Figure 2: NEMA L6-P30 Connector
NEMA L6-P30 Connector
Figure 3: IEC 330P6W Connector
IEC 330P6W Connector
Warning

The AC power cord for the router is intended for use with the router only and not for any other use.

Warning

Translation from Japanese: The attached power cable is only for this product. Do not use the cable for another product.

Note

In North America, AC power cords must not exceed 4.5 m (approximately 14.75 ft) in length, to comply with National Electrical Code (NEC) Sections 400-8 (NFPA 75, 5-2.2) and 210-52, and Canadian Electrical Code (CEC) Section 4-010(3). You can order AC power cords that are in compliance.

Warning

The router is a pluggable type A equipment installed in restricted access location. It has a separate protective earthing terminal (Metric [–M6] and English [–¼-20] screw ground lugs) provided on the chassis in addition to the grounding pin of the power supply cord. This separate protective earth terminal must be permanently connected to earth.

Caution