M120 Router Environmental Specifications
Table 1 specifies the environmental specifications required for normal router operation. In addition, the site should be as dust-free as possible.
Table 1: M120 Router Environmental Specifications
Description | Value |
---|---|
Altitude | No performance degradation to 10,000 ft (4038 m) |
Relative humidity | Normal operation ensured in relative humidity range of 5% to 90%, noncondensing |
Temperature | Normal operation ensured in temperature range of 32°F (0°C) to 104°F (40°C) Nonoperating storage temperature in shipping container: –40°F (–40°C) to 158°F (70°C) |
Seismic | Designed to meet Telcordia Technologies Zone 4 earthquake requirements |
Maximum thermal output | AC power: 7,923 BTU/hour (2322 W) DC power: 8,299 BTU/hour (2432 W) |
Install the router only in restricted areas, such as dedicated equipment rooms and equipment closets, in accordance with Articles 110-16, 110-17, and 110-18 of the National Electrical Code, ANSI/NFPA 70.