Removing a DC Power Supply on the SRX650 Services Gateway

Up to two power supplies can be located at the rear of the chassis on the right side. Each DC power supply weighs approximately 2 lbs, 13.4 oz (1.29 kg).

Caution: Do not leave a power supply slot empty for more than 30 minutes while the services gateway is operational. For proper airflow, the power supply must remain in the chassis, or a blank panel must be used in an empty slot.

Note: After powering off a power supply, wait at least 60 seconds before turning it back on.

To remove a DC power supply, see Figure 23.

  1. Switch off the dedicated facility circuit breaker for the power supply. Follow the electrostatic discharge (ESD) and disconnection instructions for your site.
  2. Make sure that the voltage across the DC power source cable leads is 0 V and that there is no chance that the cables might become active during the removal process.
  3. Attach an ESD grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis. For more information about ESD, see Preventing Electrostatic Discharge Damage to the SRX650 Services Gateway.
  4. Remove the clear plastic cover protecting the terminal studs on the faceplate.
  5. Remove the screws and washers from the terminals. Use a number 2 Phillips screwdriver to loosen and remove the screws.
  6. Remove the cable lugs from the terminal studs.
  7. Carefully move the power cables out of the way.
  8. Push the tab on the left edge of the power supply to the right.
  9. Pull the power supply straight out of the chassis.

Figure 23: Removing a DC Power Supply from the SRX650 Services Gateway

Removing a DC
Power Supply from the SRX650 Services Gateway