SRX650 Services Gateway Environmental Specifications
Table 29 provides the required environmental conditions for normal SRX650 Services Gateway operations. In addition, the site must be as dust-free as possible because dust can clog air intake vents and filters, reducing the efficiency of the cooling system.
Table 29: SRX650 Services Gateway Environmental Specifications
Description | Value |
---|---|
Altitude | No performance degradation to 13,000 ft (3962.4 m) |
Relative humidity | Normal operation ensured in relative humidity range of 5% to 90%, noncondensing |
Temperature | Normal operation ensured in temperature range of 32°F (0°C) to 104°F (40°C) Nonoperating storage temperature in shipping container: –40°F (–40°C) to 158°F (70°C) |
Seismic | Designed to meet Telcordia Technologies Zone 4 earthquake requirements |
Maximum thermal output | AC power: 4400 BTU/hour DC power with one 645 W power supply unit: 2200 BTU/hour DC power with two 645 W power supply units, nonredundant: 4400 BTU/hour Note: These specifications are estimates and subject to change. |
![]() | Note: Install the services gateway only in restricted areas, such as dedicated equipment rooms and equipment closets, in accordance with Articles 110–16, 110–17, and 110–18 of the National Electrical Code, ANSI/NFPA 70. |