AC Power Cord Specifications for the SRX5800 Services Gateway
Each AC power supply has a single AC appliance inlet located in the chassis directly above the power supply that requires a dedicated AC power feed. Most sites distribute power through a main conduit that leads to frame-mounted power distribution panels, one of which can be located at the top of the rack that houses the services gateway. An AC power cord connects each power supply to the power distribution panel.
The services gateway is not shipped with AC power cords. You must order power cords separately using the model number shown in Table 37. The C19 appliance coupler at the female end of the cord inserts into the AC appliance inlet coupler, type C20 (right angle) as described by International Electrotechnical Commission (IEC) standard 60320. The plug at the male end of the power cord fits into the power source receptacle that is standard for your geographical location.
Table 37 provides specifications and Figure 88 depicts the plug on the AC power cord provided for each country or region.
Table 37: AC Power Cord Specifications
Country | Model Number | Electrical Specification | Plug Type |
---|---|---|---|
Australia | CBL-M-PWR-RA-AU | 240 VAC, 50 Hz AC | SAA/3 |
China | CBL-M-PWR-RA-CH | 220 VAC, 50 Hz AC | PSB-10 |
Europe (except Denmark, Italy, Switzerland, and United Kingdom) | CBL-M-PWR-RA-EU | 220 or 230 VAC, 50 Hz AC | CEE 7/7 |
Italy | CBL-M-PWR-RA-IT | 230 VAC, 50 Hz AC | CEI 23-16/VII |
Japan | CBL-M-PWR-RA-JP | 220 VAC, 50 or 60 Hz AC | NEMA L6-20P |
North America | CBL-M-PWR-RA-TWLK-US | 250 VAC, 60 Hz AC | NEMA L6-20P |
United Kingdom | CBL-M-PWR-RA-UK | 240 VAC, 50 Hz AC | BS89/13 |
Figure 88: AC Plug Types

![]() | Warning: The AC power cord for the services gateway is intended for use with the services gateway only and not for any other use. |
![]() | Note: In North America, AC power cords must not exceed 4.5 m (approximately 14.75 ft) in length, to comply with National Electrical Code (NEC) Sections 400-8 (NFPA 75, 5-2.2) and 210-52, and Canadian Electrical Code (CEC) Section 4-010(3). The cords listed in Table 37 are in compliance. |
![]() | Warning: The services gateway is a pluggable type A equipment installed in restricted access location. It has a separate protective earthing terminal [Metric -M6 and English - ¼-20 screw) ground lugs] provided on the chassis in addition to the grounding pin of the power supply cord. This separate protective earth terminal must be permanently connected to earth. |
![]() | Caution: Power cords and cables must not block access to services gateway components or drape where people could trip on them. |