SRX5800 Services Gateway Environmental Specifications
Table 32 specifies the environmental specifications required for normal services gateway operation. In addition, the site should be as dust-free as possible.
Table 32: Services Gateway Environmental Specifications
Description | Value |
---|---|
Altitude | No performance degradation to 10,000 ft (3048 m) |
Relative humidity | Normal operation ensured in relative humidity range of 5% to 90%, noncondensing |
Temperature | Normal operation ensured in temperature range of 32°F (0°C) to 104°F (40°C) Nonoperating storage temperature in shipping crate: –40°F (–40°C) to 158°F (70°C) |
Seismic | Tested to meet Telcordia Technologies Zone 4 earthquake requirements |
Maximum thermal output | AC power: 20,160, BTU/hour (5912 W) DC power: 17,057 BTU/hour (5002 W) Note: These specifications are estimates and subject to change. |
![]() | Note: Install the services gateway only in restricted areas, such as dedicated equipment rooms and equipment closets, in accordance with Articles 110-16, 110-17, and 110-18 of the National Electrical Code, ANSI/NFPA 70. |