SRX5600 Services Gateway Environmental Specifications

Table 28 specifies the environmental specifications required for normal services gateway operation. In addition, the site should be as dust-free as possible.

Table 28: Services Gateway Environmental Specifications

Description

Value

Altitude

No performance degradation to 10,000 ft (3048 m)

Relative humidity

Normal operation ensured in relative humidity range of 5% to 90%, noncondensing

Temperature

Normal operation ensured in temperature range of 32°F (0°C) to 104°F (40°C)

Nonoperating storage temperature in shipping container: –40°F (–40°C) to 158°F (70°C)

Seismic

Designed to meet Telcordia Technologies Zone 4 earthquake requirements

Maximum thermal output

AC power: 11,322.8 BTU/hour (3,318  W)

DC power: 9,632 BTU/hour (2,823 W)

Note: Install the services gateway only in restricted areas, such as dedicated equipment rooms and equipment closets, in accordance with Articles 110-16, 110-17, and 110-18 of the National Electrical Code, ANSI/NFPA 70.

Related Documentation