Power Requirements for DC-Powered SRX3600 Services Gateways
![]() | Note: If you plan to operate a maximally configured DC-powered services gateway, we recommend that you provision 45 A @ -48 VDC for the system. |
If you do not plan to provision 45 A @ -48 VDC for the system, you can use the information in Table 34 and Table 35 to calculate the power consumption @ -48 VDC, and thermal output for various hardware configurations.
Table 34 lists the power requirements for base DC-powered services gateways operating under typical voltage conditions.
Table 34: DC-Powered Base System Requirements
DC Power Supply Configuration | Power Requirement (Watts) |
---|---|
Nonredundant configuration includes two DC power supplies, midplane, SFB, Routing Engine, and fan tray | 375 W (approximate) |
Redundant configuration includes four DC power supplies, midplane, SFB, Routing Engine, and fan tray | 430 W (approximate) |
![]() | Note: The power requirement values shown in Table 34 are for a lightly loaded system. For a heavily loaded system, the contribution of the base system to the overall system power requirement is lower, because the power supply efficiency improves as the load increases. For a heavily loaded system, both the redundant and nonredundant base systems contribute approximately 375 W to the overall system power requirement. |
Table 35 lists the power requirements for various hardware components when the services gateway is operating under typical voltage conditions.
Table 35: Component DC Power Requirements
Component | Power Requirement (Watts) | 48V Input Power Requirement at 80% Power Supply Efficiency |
---|---|---|
Routing Engine | 53 W | 66 W |
SPC | 118 W | 148 W |
NPC | 64 W | 80 W |
SCM | 35 W | 44 W |
IOC (max) | 40 W | 50 W |
IOC (min) | 52 W | 65 W |
Use the information in Table 34 and Table 35 to calculate power consumption for various hardware configurations, input current from a different source voltage, and thermal output, as shown in the following examples. These examples use maximum values per IOC.
Typical power consumption for DC-powered services gateways:
- Minimum DC-powered configuration:Base services gateway (nonredundant) + 1 SPC + 1 NPC =375 W + 148 W + 80W = 603 W @ -48 VDC = 12.6 A
- Maximum
DC-powered configuration:Base services gateway (redundant) + 7 SPCs + 3 NPCs + 2 IOC (max) + 1 SCM =375 W + 7(148) W + 3(80) W + 2(65) W + 44 W = 375 W + 1036 W + 240 W + 130 W + 44 W = 1825 W @ -48 VDC = 38.0 A
- Input current from a DC source other than -48 VDC
(based on maximum configuration; applies to DC power supply only):(–54 VDC input) * (input current X) = (-48 VDC input) * (input current Y)54 * X = 48 * 38.0 AX = (48 *38.0)/54 = 33.8 A
- Thermal output for maximally configured DC-powered services
gateway:Watts DC * 3.41= BTU/hr1825 * 3.41 = 6223 BTU/hr