SRX220 Services Gateway Rack Requirements

The services gateway can be installed in a rack. Many types of racks are acceptable, including front-mount racks and four-post (telco) racks.

Note: The services gateway cannot be center-mounted in racks.

Table 15 provides the details on rack size, clearance, and airflow requirements.

Table 15: Rack Requirements for the Services Gateway

Rack Requirements

Specifications

Rack size

A 19 in. (48.3 cm) rack as defined in Cabinets, Racks, Panels, and Associated Equipment (document number EIA-310-D) published by the Electronics Industry Association (http://www.eia.org).

Rack requirements

  • The outer edges of the mounting brackets extend the width the chassis to 19 in. (48.3 cm).
  • The front of the chassis extends approximately 0.5 in. (1.27 cm) beyond the mounting brackets.
  • The maximum permissible ambient temperature is 40°C.

Spacing of mounting bracket and flange holes

  • The holes within each rack set are spaced at 1 U (1.75 in. [4.5 cm]). The device can be mounted in any rack that provides holes or hole patterns spaced at 1-U (1.75 in. [4.5 cm]) increments.
  • The mounting brackets and front-mount flanges used to attach the chassis to a rack are designed to fasten to holes spaced at rack distances of 1 U (1.75 in.).
  • The mounting holes in the mounting brackets provided with the device are spaced 1.25 in. (3.2 cm) apart (top and bottom mounting holes).

Connecting to the building structure

Always secure the rack in which you are installing the services gateway to the structure of the building. If your geographical area is subject to earthquakes, bolt the rack to the floor. For maximum stability, also secure the rack to ceiling brackets.