Tools and Parts Required for Installation

 

To install the Juniper Networks EX9253 Ethernet Switch on a rack, you need:

  • Two rear mounting brackets—preinstalled

  • Eight screws to secure the switch to the rack—not provided

  • Cable management brackets and screws to attach the brackets to the chassis—provided

  • (Optional) Air filter unit—provided

  • Phillips (+) screwdriver, number 2—not provided

  • An electrostatic discharge (ESD) wrist strap with cable—provided

To connect the switch to earth ground, you need:

  • A 14 AWG ground terminal lug sized for #10 screw (Panduit LCD10-14B-L or equivalent)—provided

  • A grounding cable (minimum 14–10 AWG (2–5.3 mm²), minimum 60°C wire or as permitted by local code)—not provided

  • A pair of M5 Pan Head screws—provided

To connect AC power to the switch, you need:

  • An AC power supply installed in the switch—provided

  • An AC power cord with a plug appropriate for your geographical location—provided

  • A power cord retainer—provided

  • An external management device—not provided

To connect DC power to the switch, you need:

  • A DC power supply installed in the switch—provided

  • Two DC power source cables (minimum 10 AWG (1.3 mm²), minimum 60°C wire or as permitted by local code)—not provided

  • Two 16-14 AWG ring lugs sized for #6 screws (Panduit PN10-10R or equivalent)—provided

  • A torque-controlled socket nut driver, with a maximum torque capacity of 6 lb-in. (0.68 Nm), for tightening the screws on the terminals on each power supply—not provided

    Caution

    The maximum torque rating of the terminal screws on the DC power supply is 6 lb-in. (0.68 Nm). The terminal screws might be damaged if excessive torque is applied. Use only a torque-controlled driver to tighten screws on the DC power supply terminals. Use an appropriately sized driver, with a maximum torque capacity of 6 lb-in. (0.68 Nm) or less. Ensure that the driver is undamaged and properly calibrated and that you have been trained in its use. You may want to use a driver that is designed to prevent overtorque when the preset torque level is achieved.

  • A wire cutter—not provided

  • An external management device—not provided

To perform initial configuration of the switch, you need:

  • An Ethernet cable with an RJ-45 connector attached—provided

  • An RJ-45 to DB-9 serial port adapter—provided

  • A management host, such as a PC, with an Ethernet port—not provided

Register product serial numbers on the Juniper Networks website and update the installation base data if there is any addition or change to the installation base or if the installation base is moved. Juniper Networks will not be held accountable for not meeting the hardware replacement service-level agreement for products that do not have registered serial numbers or accurate installation base data.

Register your product(s) https://tools.juniper.net/svcreg/SRegSerialNum.jsp.

Update your install base at https://www.juniper.net/customers/csc/management/updateinstallbase.jsp.