Maintaining the MX80 Fan Tray
Purpose
For optimum cooling, verify the condition of the fans.
Action
- Monitor the status of the fans. A fan tray contains multiple fans that work in unison to cool the router components. If one fan fails, the router adjusts the speed of the remaining fans to maintain proper cooling. A red alarm is triggered when a fan fails, and a yellow alarm and red alarm is triggered when a fan tray is removed.
- To display the status of the cooling system, issue the show chassis environment command. The output is similar to the
following:
user@host> show chassis environmentClass Item Status Measurement Temp PEM 0 OK 45 degrees C / 113 degrees F PEM 1 OK 45 degrees C / 113 degrees F RE 0 Intake OK 33 degrees C / 91 degrees F RE 0 Front Exhaust OK 38 degrees C / 100 degrees F RE 0 Rear Exhaust OK 38 degrees C / 100 degrees F Routing Engine OK 33 degrees C / 91 degrees F Routing Engine CPU OK 54 degrees C / 129 degrees F TFEB 0 QX 0 TSen OK 44 degrees C / 111 degrees F TFEB 0 QX 0 Chip OK 47 degrees C / 116 degrees F TFEB 0 LU 0 TSen OK 44 degrees C / 111 degrees F TFEB 0 LU 0 Chip OK 50 degrees C / 122 degrees F TFEB 0 MQ 0 TSen OK 44 degrees C / 111 degrees F TFEB 0 MQ 0 Chip OK 49 degrees C / 120 degrees F TFEB 0 TBB PFE TSen OK 37 degrees C / 98 degrees F TFEB 0 TBB PFE Chip OK 50 degrees C / 122 degrees F TFEB 0 TFEB PCIE TSen OK 45 degrees C / 113 degrees F TFEB 0 TFEB PCIE Chip OK 68 degrees C / 154 degrees F Fans Fan 1 OK Spinning at intermediate-speed Fan 2 OK Spinning at intermediate-speed Fan 3 OK Spinning at intermediate-speed Fan 4 OK Spinning at intermediate-speed Fan 5 OK Spinning at intermediate-speed