Technical Documentation

T1600 Three-Input 240-A DC Power Supply Specifications

Table 1 lists the three-input 240-A DC power supply electrical specifications.

Table 1: Power Supply Electrical Specifications

Item

Specification

DC input voltage

Nominal –48 VDC, –60 VDC
Operating range: –40.0 to –72.0 VDC

Note: If the input voltage from the DC power source drops below -37.5 to -39.5 VDC, the routing platform automatically shuts down. During automatic shutdown, the circuit remains active. When the input voltage returns to –43.0 to –44.00 VDC, the router automatically starts up again and the system returns to normal operation within 30 minutes. No operator intervention is required.

Input DC current rating

Part number:

  • Input 0: 47 A @ –48 VDC (nominal) (2256 W)
  • Input 1: 67 A @ –48 VDC (nominal) (3216 W)
  • Input 2: 67 A @ –48 VDC (nominal) (3216 W)

Part number:

  • Input 0: 54 A @ –48 VDC (nominal) (2592 W)
  • Input 1: 67 A @ –48 VDC (nominal) (3216 W)
  • Input 2: 67 A @ –48 VDC (nominal) (3216 W)