T1600 DC Power Distribution

Most sites distribute DC power through a main conduit that leads to frame-mounted DC power distribution panels, one of which might be located at the top of the rack that houses the router. A pair of cables (one input and one return) connects each set of terminal studs to the power distribution panel.

Note: All inputs on the DC power supply in slot PEM0 must be powered by dedicated power feeds derived from feed A, and all inputs on the DC power supply in slot PEM 1 must be powered by dedicated power feeds derived from feed B. This configuration provides the commonly deployed A/B feed redundancy for the system.

Figure 1 shows a typical DC source cabling arrangement.

Figure 1: Typical DC Source Cabling to the Router

Image g002411.gif