DC Power Cable Specifications for the MX480 Router
DC Power Cable Lug Specifications—The accessory box shipped with the router includes the cable lugs that attach to the terminal studs of each power supply (see Figure 1).
Figure 1: DC Power Cable Lug

![]() | Caution: Before router installation begins, a licensed electrician must attach a cable lug to the grounding and power cables that you supply. A cable with an incorrectly attached lug can damage the router. |
![]() | Note: The same cable lug is used for the grounding cable. |
DC Power Cable Specifications—Table 1 summarizes the specifications for the power cables, which you must supply.
Table 1: DC Power Cable Specifications
Cable Type | Quantity and Specification |
|---|---|
Power | Eight 6-AWG (13.3 mm2), minimum 60°C wire, or as required by the local code |