We recommend that you use a standard EIA distribution rack. See Equipment Rack Requirements for detailed rack information.
Before installing the systems in a rack, consider the following guidelines and refer to Figure 15:
Installing multiple systems in a single rack enables you to maximize your available space.
![]() |
Caution: If you install an ERX-7xx model or ERX-310 router directly above an ERX-14xx model in the same rack, you must install a plenum between the ERX-7xx model or ERX-310 router and the ERX-14xx model so that the air can circulate between the systems. (See Figure 53.) This plenum is available from Juniper Networks. |
If you install an ERX-14xx model above an ERX-7xx model or ERX-310 router, there is no need to install a plenum between the units because the ERX-7xx models and ERX-310 routers vent air out the side of the chassis.
Figure 15: ERX Routers Installed in Recommended Order

Observe the following safety guidelines when mounting the router in a rack.
![]() |
Warning: Install equipment in the rack from the bottom upward. This helps to maintain the stability of the rack and reduces the chance of the rack tipping over. |
![]() |
Warning: Three people are required to install the router in a rack: two to lift the system into position and one to screw it to the rack. |
![]() |
Caution: Evaluate the overall loading of the branch circuit before you install any equipment into a rack. |
![]() |
Warning: Connect the router or rack to ground (earth), and ensure that a reliable grounding path is maintained in the rack. |
![]() |
Warning: Do not work on the system or connect or disconnect cables during lightning activity. |
![]() |
Warning: Be sure circuit breakers for the power source are in the OFF position before attaching power cables. |
![]() |
Warning: Before servicing the router, turn off the power. |
![]() |
Warning: Remove jewelry (including rings, necklaces, and watches) before working on equipment that is connected to power lines. Metal objects heat up when connected to power and ground and can cause serious burns or become welded to the terminals. |
![]() |
Warning: Do not insert any metal object, such as a screwdriver, into an open slot or the backplane. Doing so can cause electric shock and serious burns. |
![]() |
Warning: The ERX-310 router AC model has more than one power-supply cord. Disconnect two power cords before servicing to avoid electric shock. |
Following your installation plan, use a tape measure and marking pen to measure and mark space on each equipment rack for each router component. For horizontal spacing, follow Network Equipment Building System (NEBS) requirements. If you choose not to install a plenum, be sure to include 2 U of space between each chassis for proper exhaust. A plenum, however, is highly recommended.
To complete the installation of the router in a rack, you need:
![]() |
Warning: Three people are required to install the router in a rack: two to lift the system into position and one to screw it to the rack. |
![]() |
Caution: Make sure all persons handling a router wear an antistatic device. |
To install the router in the rack:
Figure 15 illustrates a distribution rack with one ERX-310 router, one ERX-7xx model, and one ERX-14xx model installed.