temperature-sensor
语法
temperature-sensor sensor-name { temperature-threshold { fans-on-full-speed fans-full-speed-temp; fans-on-full-speed-if-failed-fan full-speed-failed-fan-temp; fans-on-intermediate-speed fans-intermediate-speed-temp; fans-to-normal-speed fans-normal-speed-temp; fire-shutdown fire-shutdown-temp; red-alarm red-alarm-temp; red-alarm-if-failed-fan red-alarm-failed-fan-temp; yellow-alarm yellow-alarm-temp; yellow-alarm-if-failed-fan yellow-alarm-failed-fan-temp; } }
层次结构级别
[edit chassis cb 0] [edit chassis fpc fpc_number]
描述
使用 temperature-sensor
命令修改风扇速度变化的温度阈值,以对 Junos OS 和 Junos OS 演化版中的 400G ZR 和 ZR-M 等高功率光学器件进行热管理。如果您的平台和软件版本支持 光学电磁策略,则不需要此手动配置。
支持光学 EM 策略的平台和软件版本不需要为高功率光学器件(例如 400G ZR/ZR+)手动配置风扇速度。光学电磁策略将可插拔光学模块的定期轮询温度读数纳入系统对风扇速度行为的自动控制中。请查看 功能浏览器 以验证您的设备和软件版本是否支持光学电磁策略。
仅以下平台和版本支持该命令:
平台 | 发布 |
---|---|
PTX10K 与 PTX10K-LC1201-36CD | Junos Evolved 23.4R1 之前的版本 |
PTX10001-36MR | Junos Evolved 23.4R1 之前的版本 |
ACX7100-32C、ACX7100-48L | Junos Evolved 24.4R1 之前的版本 |
MX10K 与 MX10K-LC9600 | Junos 24.4R1 版之前的版本 |
MX304 和 MX304-LMIC16 | Junos 24.2R1 版之前的版本 |
选项
选项 |
描述 |
---|---|
温度传感器 sensor-name |
如果温度传感器的名称包含空格,则用引号指定该名称。 sensor-name 使用如下所示:
请使用 |
温度阈值 |
指定温度阈值。 |
风扇全速fans-full-speed-temp开启 | 温度阈值基于全速风扇的机箱冷却要求。 |
风扇开启全速故障风扇 full-speed-failed-fan-temp | 温度阈值基于风扇全速且任何风扇出现故障时的机箱冷却要求。 |
中速风扇 fans-intermediate-speed-temp | 温度阈值基于风扇处于中速时的机箱冷却要求。 |
风扇至正常速度 fans-normal-speed-temp | 基于风扇在正常速度下的机箱冷却要求测定的温度阈值。 |
防火关断 fire-shutdown-temp |
超过该阈值 Junos 将触发火火关闭。 |
红色报警 red-alarm-temp |
温度阈值,超过该阈值 Junos 将触发红色警报。 |
红色报警-if-failed-fan red-alarm-failed-fan-temp |
温度阈值,超过该阈值,当任何风扇发生故障时,Junos 将触发红色警报。 |
黄色报警 yellow-alarm-temp |
温度阈值,超过该阈值 Junos 将触发黄色警报。 |
黄色警报-if-failed-fan yellow-alarm-failed-fan-temp |
温度阈值,超过该阈值,当任何风扇发生故障时,Junos 将触发黄色警报。 |
配置温度阈值时,必须保持以下顺序:
fans-to-normal-speed-temp
fans-on-intermediate-speed-temp
< < fans-full-speed-temp
<= yellow-alarm-temp
< red-alarm-temp
<fire-shutdown-temp
以下代码片段是多个平台的温度阈值(以摄氏度为单位)配置示例。
- PTX10001-36MR
- PTX10K-LC1201-36CD 线卡,用于PTX10004、PTX10008和PTX10016
- ACX7100-48L
- ACX7100-32C型
- MX10K-LC9600 线卡,用于MX10004和MX10008
- 用于 MX304 的 MX304-LMIC16 线卡
- 验证配置的阈值
PTX10001-36MR
[edit chassis cb 0] temperature-sensor "Temp Sensor PSM Inlet" { temperature-threshold { fans-on-full-speed 30; fans-on-full-speed-if-failed-fan 28; fans-on-intermediate-speed 20; fans-to-normal-speed 15; fire-shutdown 80; red-alarm 75; red-alarm-if-failed-fan 72; yellow-alarm 65; yellow-alarm-if-failed-fan 62; } }
PTX10K-LC1201-36CD 线卡,用于PTX10004、PTX10008和PTX10016
[edit chassis cb 0] temperature-sensor "Intake A Temp Sensor" { temperature-threshold { fans-on-full-speed 3; fans-on-full-speed-if-failed-fan 0; fans-on-intermediate-speed 2; fans-to-normal-speed 1; fire-shutdown 80; red-alarm 75; red-alarm-if-failed-fan 72; yellow-alarm 65; yellow-alarm-if-failed-fan 62; } }
ACX7100-48L
JCO400-QDD-ZR、JCO400-QDD-ZR-M、QDD-400G-ZR-M、QDD-400G-ZR-M-HP 光学模块
[edit chassis fpc fpc_number] temperature-sensor xcvr-0/0/1 { temperature-threshold { fans-on-full-speed 38; fans-on-full-speed-if-failed-fan 38; fans-on-intermediate-speed 26; fans-to-normal-speed 21; fire-shutdown 90; red-alarm 80; red-alarm-if-failed-fan 80; yellow-alarm 70; yellow-alarm-if-failed-fan 70; } } temperature-sensor xcvr-0/0/2 { temperature-threshold { fans-on-full-speed 38; fans-on-full-speed-if-failed-fan 38; fans-on-intermediate-speed 26; fans-to-normal-speed 21; fire-shutdown 90; red-alarm 80; red-alarm-if-failed-fan 80; yellow-alarm 70; yellow-alarm-if-failed-fan 70; } }
ACX7100-32C型
JCO400-QDD-ZR、JCO400-QDD-ZR-M、QDD-400G-ZR、QDD-400G-ZR-M、QDD-400G-ZR-M-HP 光学模块
[edit chassis fpc fpc_number] temperature-sensor xcvr-0/0/1 { temperature-threshold { fans-on-full-speed 30; fans-on-full-speed-if-failed-fan 30; fans-on-intermediate-speed 21; fans-to-normal-speed 16; fire-shutdown 100; red-alarm 90; red-alarm-if-failed-fan 90; yellow-alarm 80; yellow-alarm-if-failed-fan 80; } } temperature-sensor xcvr-0/0/2 { temperature-threshold { fans-on-full-speed 34; fans-on-full-speed-if-failed-fan 34; fans-on-intermediate-speed 25; fans-to-normal-speed 20; fire-shutdown 100; red-alarm 90; red-alarm-if-failed-fan 90; yellow-alarm 80; yellow-alarm-if-failed-fan 80; } }
MX10K-LC9600 线卡,用于MX10004和MX10008
[edit chassis fpc fpc_number] temperature-sensor "Intake-A Temp Sensor" { temperature-threshold { fans-on-full-speed 3; fans-on-full-speed-if-failed-fan 0; fans-on-intermediate-speed 2; fans-to-normal-speed 1; fire-shutdown 80; red-alarm 75; red-alarm-if-failed-fan 72; yellow-alarm 65; yellow-alarm-if-failed-fan 62; } }
fpc_number是安装 MX10K-LC9600 线卡的 FPC。
用于 MX304 的 MX304-LMIC16 线卡
[edit chassis cb 0] temperature-sensor Intake_A Temp Sensor { temperature-threshold { fans-to-normal-speed 5; fans-on-intermediate-speed 15; fans-on-full-speed 20; fans-on-full-speed-if-failed-fan 17; yellow-alarm 50; yellow-alarm-if-failed-fan 50; red-alarm 70; red-alarm-if-failed-fan 70; fire-shutdown 75; } }
验证配置的阈值
您可以使用以下命令验证配置的阈值 show chassis temperature-thresholds
:
user@host> show chassis temperature-thresholds Fan speed Yellow alarm Red alarm Fire Shutdown (degrees C) (degrees C) (degrees C) (degrees C) Item Normal High Normal Bad fan Normal Bad fan Normal Routing Engine 0 Temp Sensor Exhaust Left 65 70 80 78 85 82 90 Routing Engine 0 Temp Sensor Exhaust Middle 65 70 80 78 85 82 90 Routing Engine 0 Temp Sensor Exhaust Right 65 70 80 78 85 82 90 Routing Engine 0 CPU Temperature 72 77 88 85 95 92 98 CB 0 Temp Sensor Left 1 51 55 70 68 75 72 80 CB 0 Temp Sensor Left 2 75 80 90 87 95 92 98 CB 0 Temp Sensor PSM Inlet 39 43 65 62 75 72 80 CB 0 Temp Sensor Exhaust 90 95 112 110 116 114 120 CB 0 Temp Sensor Exhaust Bottom 70 75 85 82 90 87 95 CB 0 Inlet-1 75 80 90 87 95 92 98 CB 0 Temp Sensor Exhaust Right 1 75 80 90 87 95 92 98 CB 0 Temp Sensor Exhaust Right 2 75 80 90 87 95 92 98 FPC 0 BT-0 HBM-0 Temperature 80 85 103 100 105 103 110 FPC 0 BT-0 HBM-1 Temperature 80 85 103 100 105 103 110 FPC 0 BT-0 TVsense Temp Max 95 100 120 117 124 120 130 FPC 0 BT-1 HBM-0 Temperature 80 85 103 100 105 103 110 FPC 0 BT-1 HBM-1 Temperature 80 85 103 100 105 103 110 FPC 0 BT-1 TVsense Temp Max 95 100 120 117 124 120 130 FPC 0 BT-2 HBM-0 Temperature 80 85 103 100 105 103 110 FPC 0 BT-2 HBM-1 Temperature 80 85 103 100 105 103 110 FPC 0 BT-2 TVsense Temp Max 95 100 120 117 124 120 130 FPC 0 WAN RT0.0 82 87 107 104 110 107 115 FPC 0 WAN RT0.1 82 87 107 104 110 107 115 FPC 0 WAN RT1.0 82 87 107 104 110 107 115 FPC 0 WAN RT1.1 82 87 107 104 110 107 115 FPC 0 WAN RT2.0 82 87 107 104 110 107 115 FPC 0 WAN RT2.1 82 87 107 104 110 107 115 FPC 0 BT-0 Temp sensor 0 95 100 120 117 124 120 130 FPC 0 BT-0 Temp sensor 1 95 100 120 117 124 120 130 FPC 0 BT-1 Temp sensor 0 95 100 120 117 124 120 130 FPC 0 BT-1 Temp sensor 1 95 100 120 117 124 120 130 FPC 0 BT-2 Temp sensor 0 95 100 120 117 124 120 130 FPC 0 BT-2 Temp sensor 1 95 100 120 117 124 120 130 SIB 0 ASIC Temp, ZF0 80 85 115 112 121 117 125 FPC 0 xcvr-0/0/1 47 52 70 70 74 74 75 FPC 0 xcvr-0/0/4 50 55 73 73 76 76 77 FPC 0 xcvr-0/0/5 47 52 70 70 75 75 76
所需权限级别
接口 — 要在配置中查看此语句。
interface-control - 将此语句添加到配置中。
发布信息
在 Junos OS 22.3R1 版中引入的语句。