To install a DC power supply (see Figure 3):
![]() |
Caution: You must ensure that power connections maintain the proper polarity. The power source cables might be labeled (+) and (–) to indicate their polarity. There is no standard color coding for DC power cables. The color coding used by the external DC power source at your site determines the color coding for the leads on the power cables that attach to the terminal studs on each power supply. |
![]() |
Note: For the SRX 5600 services gateway, the DC power supply in PEM0 and PEM1 must be powered by dedicated power feeds derived from feed A, and the DC power supply in PEM2 and PEM3 must be powered by dedicated power feeds derived from feed B. This configuration provides the commonly deployed A/B feed redundancy for the system. |
![]() |
Note: For information about connecting to DC power sources, see the SRX 5600 Services Gateway Hardware Guide. |
![]() |
Note: If more than one power supply is being installed, turn on all power supplies at the same time. |
![]() |
Note: An SCB must be present for the PWR OK LED to go on. |
Figure 3: Installing a DC Power Supply

Figure 4: Connecting DC Power