During normal operation:
The following alarms, LEDs, and other indications indicate a problem with the cooling system:
To troubleshoot the cooling system:
user@host> show chassis fansfc0-re0:
--------------------------------------------------------------------------
Item Status RPM Measurement
Fan Tray 0 Fan 1 OK 3450 Spinning at normal speed
Fan Tray 0 Fan 2 OK 3420 Spinning at normal speed
Fan Tray 0 Fan 3 OK 3480 Spinning at normal speed
Fan Tray 0 Fan 4 OK 3360 Spinning at normal speed
Fan Tray 0 Fan 5 OK 3360 Spinning at normal speed
Fan Tray 0 Fan 6 OK 3390 Spinning at normal speed
Fan Tray 1 Fan 1 OK 3420 Spinning at normal speed
Fan Tray 1 Fan 2 OK 3450 Spinning at normal speed
Fan Tray 1 Fan 3 OK 3450 Spinning at normal speed
Fan Tray 1 Fan 4 OK 3420 Spinning at normal speed
Fan Tray 1 Fan 5 OK 3480 Spinning at normal speed
Fan Tray 1 Fan 6 OK 3420 Spinning at normal speed
Fan Tray 2 Fan 1 OK 3420 Spinning at normal speed
Fan Tray 2 Fan 2 OK 3420 Spinning at normal speed
Fan Tray 2 Fan 3 OK 3420 Spinning at normal speed
Fan Tray 2 Fan 4 OK 3390 Spinning at normal speed
Fan Tray 2 Fan 5 OK 3450 Spinning at normal speed
Fan Tray 2 Fan 6 OK 3360 Spinning at normal speed
Fan Tray 2 Fan 7 OK 3390 Spinning at normal speed
Fan Tray 2 Fan 8 OK 3420 Spinning at normal speed
user@host> show chassis environment sfc 0sfc0-re0:
--------------------------------------------------------------------------
Class Item Status Measurement
Temp PEM 0 OK 28 degrees C / 82 degrees F
PEM 1 Absent
Routing Engine 0 OK 27 degrees C / 80 degrees F
Routing Engine 1 OK 29 degrees C / 84 degrees F
CB 0 Intake OK 26 degrees C / 78 degrees F
CB 0 Exhaust A OK 25 degrees C / 77 degrees F
CB 0 Exhaust B OK 25 degrees C / 77 degrees F
CB 1 Intake OK 26 degrees C / 78 degrees F
CB 1 Exhaust A OK 26 degrees C / 78 degrees F
CB 1 Exhaust B OK 26 degrees C / 78 degrees F
SIB F13 0 OK 47 degrees C / 116 degrees F
SIB F13 0 (B) OK 48 degrees C / 118 degrees F
SIB F13 1 OK 38 degrees C / 100 degrees F
SIB F13 1 (B) OK 37 degrees C / 98 degrees F
SIB F2S 0/0 OK 27 degrees C / 80 degrees F
SIB F2S 0/2 OK 28 degrees C / 82 degrees F
SIB F2S 0/4 OK 27 degrees C / 80 degrees F
SIB F2S 0/6 OK 28 degrees C / 82 degrees F
SIB F2S 1/0 OK 26 degrees C / 78 degrees F
SIB F2S 1/2 OK 26 degrees C / 78 degrees F
SIB F2S 1/4 OK 26 degrees C / 78 degrees F
SIB F2S 1/6 OK 26 degrees C / 78 degrees F
SIB F2S 2/0 OK 25 degrees C / 77 degrees F
SIB F2S 2/2 OK 25 degrees C / 77 degrees F
SIB F2S 2/4 OK 23 degrees C / 73 degrees F
CIP 0 Intake OK 23 degrees C / 73 degrees F
CIP 0 Exhaust A OK 24 degrees C / 75 degrees F
CIP 0 Exhaust B OK 24 degrees C / 75 degrees F
CIP 1 Intake OK 24 degrees C / 75 degrees F
CIP 1 Exhaust A OK 25 degrees C / 77 degrees F
CIP 1 Exhaust B OK 25 degrees C / 77 degrees F
Fans Fan Tray 0 Fan 1 OK Spinning at normal speed
Fan Tray 0 Fan 2 OK Spinning at normal speed
Fan Tray 0 Fan 3 OK Spinning at normal speed
Fan Tray 0 Fan 4 OK Spinning at normal speed
Fan Tray 0 Fan 5 OK Spinning at normal speed
Fan Tray 0 Fan 6 OK Spinning at normal speed
Fan Tray 1 Fan 1 OK Spinning at normal speed
Fan Tray 1 Fan 2 OK Spinning at normal speed
Fan Tray 1 Fan 3 OK Spinning at normal speed
Fan Tray 1 Fan 4 OK Spinning at normal speed
Fan Tray 1 Fan 5 OK Spinning at normal speed
Fan Tray 1 Fan 6 OK Spinning at normal speed
Fan Tray 2 Fan 1 OK Spinning at normal speed
Fan Tray 2 Fan 2 OK Spinning at normal speed
Fan Tray 2 Fan 3 OK Spinning at normal speed
Fan Tray 2 Fan 4 OK Spinning at normal speed
Fan Tray 2 Fan 5 OK Spinning at normal speed
Fan Tray 2 Fan 6 OK Spinning at normal speed
Fan Tray 2 Fan 7 OK Spinning at normal speed
Fan Tray 2 Fan 8 OK Spinning at normal speed
Fan Tray 2 Fan 9 OK Spinning at normal speed
Fan Tray 3 Fan 1 OK Spinning at normal speed
Fan Tray 3 Fan 2 OK Spinning at normal speed
Fan Tray 3 Fan 3 OK Spinning at normal speed
Fan Tray 3 Fan 4 OK Spinning at normal speed
Fan Tray 3 Fan 5 OK Spinning at normal speed
Fan Tray 3 Fan 6 OK Spinning at normal speed
Fan Tray 3 Fan 7 OK Spinning at normal speed
Fan Tray 3 Fan 8 OK Spinning at normal speed
Fan Tray 3 Fan 9 OK Spinning at normal speed
Fan Tray 4 Fan 1 OK Spinning at normal speed
Fan Tray 4 Fan 2 OK Spinning at normal speed
Fan Tray 4 Fan 3 OK Spinning at normal speed
Fan Tray 4 Fan 4 OK Spinning at normal speed
Fan Tray 4 Fan 5 OK Spinning at normal speed
Fan Tray 4 Fan 6 OK Spinning at normal speed
Fan Tray 4 Fan 7 OK Spinning at normal speed
Fan Tray 4 Fan 8 OK Spinning at normal speed
Fan Tray 4 Fan 9 OK Spinning at normal speed
Fan Tray 5 Fan 1 OK Spinning at normal speed
Fan Tray 5 Fan 2 OK Spinning at normal speed
Fan Tray 5 Fan 3 OK Spinning at normal speed
Fan Tray 5 Fan 4 OK Spinning at normal speed
Fan Tray 5 Fan 5 OK Spinning at normal speed
Fan Tray 5 Fan 6 OK Spinning at normal speed
Fan Tray 5 Fan 7 OK Spinning at normal speed
Fan Tray 5 Fan 8 OK Spinning at normal speed
Fan Tray 5 Fan 9 OK Spinning at normal speed
Misc SPMB 0 OK
SPMB 1 OK
user@host> show chassis temperature-thresholdsFan speed Yellow alarm Red alarm Item Normal High Normal Bad fan Normal Bad fan Chassis default 48 54 65 55 75 65 Routing Engine 0 48 54 85 85 100 100 Routing Engine 1 48 54 85 85 100 100 SIB F13 0 64 70 76 72 90 84 SIB F13 1 64 70 76 72 90 84 SIB F13 3 64 70 76 72 90 84 SIB F13 4 64 70 76 72 90 84 SIB F13 6 64 70 76 72 90 84 SIB F13 7 64 70 76 72 90 84 SIB F13 8 64 70 76 72 90 84 SIB F13 9 64 70 76 72 90 84 SIB F13 12 64 70 76 72 90 84 SIB F2S 16 64 70 76 72 90 84 SIB F2S 17 64 70 76 72 90 84 SIB F2S 18 64 70 76 72 90 84 SIB F2S 19 64 70 76 72 90 84 SIB F2S 20 64 70 76 72 90 84 SIB F2S 21 64 70 76 72 90 84 SIB F2S 22 64 70 76 72 90 84 SIB F2S 23 64 70 76 72 90 84 SIB F2S 24 64 70 76 72 90 84 SIB F2S 25 64 70 76 72 90 84 SIB F2S 26 64 70 76 72 90 84 SIB F2S 27 64 70 76 72 90 84 SIB F2S 28 64 70 76 72 90 84 SIB F2S 29 64 70 76 72 90 84 SIB F2S 30 64 70 76 72 90 84 SIB F2S 31 64 70 76 72 90 84 SIB F2S 32 64 70 76 72 90 84 SIB F2S 33 64 70 76 72 90 84 SIB F2S 34 64 70 76 72 90 84 SIB F2S 35 64 70 76 72 90 84
user@host> show chassis alarms sfc 0For information about the alarms, see Table 1.
The text in the column labeled ”LCD Message” appears in the display of the craft interface. The text in the column labeled “CLI Message” appears in the output from the show chassis alarms command.
Table 1: TX Matrix Plus Chassis Alarm Messages for the Cooling System
Component | Alarm Type | LCD Message | CLI Message | Alarm Condition | Solution |
|---|---|---|---|---|---|
Fans | Red | Fan Failure | fan-name Failure | A fan has failed. | Replace the fan tray. |
Fans Missing | Too many fans missing or failing | A fan tray is missing or too many fan trays have failed. | Reinstall the fan tray in the chassis. | ||
Yellow | Fan Removed | fan-name Removed | A fan tray has been removed. | Reinstall the fan tray in the chassis. | |
Temperature sensors | Red | Temperature Hot | Temperature Hot | The chassis temperature exceeded the hot temperature threshold. If this condition persists, the router shuts down. |
|
Sensor Failure | Temperature sensor failure | A temperature sensor failed. | Contact JTAC. | ||
Yellow | Temperature Warm | Temperature Warm | The chassis temperature exceeded the warm temperature threshold. |
|