Home > Support > Technical Documentation > T Series Routers > TX Matrix Plus Router Hardware > Installing the TX Matrix Plus Mounting Hardware for an Open-Frame Rack
Print
Rate and give feedback:  Feedback Received. Thank You!
Rate and give feedback: 
Close
This document helped resolve my issue.  Yes No

Additional Comments

800 characters remaining

May we contact you if necessary?

Name:  
E-mail: 
Submitting...
 

Related Documentation

  • T Series
  • Rack Requirements for a TX Matrix Plus Router
  • Installing the TX Matrix Plus Mounting Hardware for a Four-Post Rack
 

Installing the TX Matrix Plus Mounting Hardware for an Open-Frame Rack

  1. Assembling the Open-Frame Rack Mounting Shelf
  2. Installing Cage Nuts, If Needed
  3. Installing the Open-Frame Rack Mounting Shelf

Assembling the Open-Frame Rack Mounting Shelf

The open-frame rack mounting shelf is shipped in three pieces: one bottom piece and two side pieces. Eight screws are provided. To assemble the open-frame rack mounting shelf:

  1. Place one side of the mounting shelf over the holes on the bottom shelf piece.
  2. Partially insert screws into the open holes in the flanges of the open-frame rack mounting shelf.
  3. Tighten all the screws completely.
  4. Place the other side of the mounting shelf over the holes on the bottom shelf piece.
  5. Partially insert screws into the open holes in the flanges of the open-frame rack mounting shelf.
  6. Tighten all the screws completely.

Installing Cage Nuts, If Needed

Insert cage nuts, if needed, into the holes listed in Table 1 and Table 2 (an X indicates a mounting hole location). The hole distances are relative to the standard U division on the rack that is aligned with the bottom of the mounting shelf and rear support bracket.

To install cage nuts in an open-frame rack:

  1. On the rear side of both rack rails, insert cage nuts in the holes specified for the open-frame mounting shelf (see Table 1).
  2. On the front side of both rack rails, insert cage nuts in the holes specified for mouting the chassis (see Table 2).

Table 1: Mounting Hole Locations for Installing a TX Matrix Plus Open-Frame Rack Shelf

Hole

Distance Above U Division

Open-Frame MountingShelf

42

24.25 in. (61.6 cm)

13.86 U

X

39

22.5 in. (57.2 cm)

12.86 U

X

36

20.75 in. (52.7 cm)

11.86 U

X

33

19.0 in. (48.3 cm)

10.86 U

X

30

17.25 in. (43.8 cm)

9.86 U

X

27

15.5 in. (39.4 cm)

8.86 U

X

24

13.75 in. (34.9 cm)

7.86 U

X

21

12.0 in. (30.5 cm)

6.86 U

X

18

10.25 in. (26.0 cm)

5.86 U

X

15

8.5 in. (21.6 cm)

4.86 U

X

12

6.75 in. (17.1 cm)

3.86 U

X

9

5.0 in. (12.7 cm)

2.86 U

X

6

3.25 in. (3.8 cm)

1.86 U

X

The holes in the center-mounting brackets are spaced at 2 U (3.5 in. or 8.9 cm).

Table 2: Mounting Hole Locations for Installing a TX Matrix Plus Chassis in an Open-Frame Rack

Hole

Distance Above U Division

Chassis

90

52.5 in. (132.7 cm)

29.86 U

X

84

48.75 in. (123.8 cm)

27.86 U

X

78

45.25 in. (114.9 cm)

25.86 U

X

72

41.75 in. (106.0 cm)

23.86 U

X

66

38.25 in. (97.2 cm)

21.86 U

X

60

34.75 in. (88.3 cm)

19.86 U

X

54

31.25 in. (79.4 cm)

17.86 U

X

48

27.75 in. (70.5 cm)

15.86 U

X

42

24.25 in. (61.6 cm)

13.86 U

X

36

20.75 in. (52.7 cm)

11.86 U

X

30

17.25 in. (43.8 cm)

9.86 U

X

24

13.75 in. (34.9 cm)

7.86 U

X

18

10.25 in. (26.0 cm)

5.86 U

X

12

6.75 in. (17.1 cm)

3.86 U

X

Installing the Open-Frame Rack Mounting Shelf

Before mounting the chassis in an open-frame rack, you must first install the open-frame rack mounting shelf.

To install the open-frame rack mounting shelf, (see Figure 1):

  1. On the rear of each rack rail, partially insert a mounting screw into the highest hole specified in Table 1 for the open-frame rack mounting shelf.
  2. Install the open-frame rack mounting shelf on the rack. Hang the shelf over the mounting screws using the keyhole slots located near the top of the shelf flanges.
  3. Partially insert screws into the open holes in the flanges of the open-frame rack mounting shelf.
  4. Tighten all the screws completely.

Figure 1: Installing the TX Matrix Plus Mounting Hardware for an Open-Frame Rack

Installing the
TX Matrix Plus Mounting Hardware for an Open-Frame Rack

Insert screws in the holes specified in Table 3 (an X indicates a mounting hole location). The hole distances are relative to the standard U division on the rack that is aligned with the bottom of the mounting shelf.

Table 3: Mounting Hole Locations for Installing a TX Matrix Plus Open-Frame Rack Shelf

Hole

Distance Above U Division

Open-Frame MountingShelf

42

24.25 in. (61.6 cm)

13.86 U

X

39

22.5 in. (57.2 cm)

12.86 U

X

36

20.75 in. (52.7 cm)

11.86 U

X

33

19.0 in. (48.3 cm)

10.86 U

X

30

17.25 in. (43.8 cm)

9.86 U

X

27

15.5 in. (39.4 cm)

8.86 U

X

24

13.75 in. (34.9 cm)

7.86 U

X

21

12.0 in. (30.5 cm)

6.86 U

X

18

10.25 in. (26.0 cm)

5.86 U

X

15

8.5 in. (21.6 cm)

4.86 U

X

12

6.75 in. (17.1 cm)

3.86 U

X

9

5.0 in. (12.7 cm)

2.86 U

X

6

3.25 in. (3.8 cm)

1.86 U

X

 

Related Documentation

  • T Series
  • Rack Requirements for a TX Matrix Plus Router
  • Installing the TX Matrix Plus Mounting Hardware for a Four-Post Rack
 

Published: 2011-12-19

 
  • About Juniper
  • The New Network
  • Investor Relations
  • Press Releases
  • Newsletters
  • Juniper Offices
  • Resources
  • How to Buy
  • Partner Locator
  • Image Library
  • Visio Templates
  • Security Center
  • Community
  • Forums
  • Blogs
  • Junos Central
  • Social Media
  • Support
  • Technical Documentation
  • Knowledge Base (KB)
  • Software Downloads
  • Product Licensing
  • Contact Support
Site Map / RSS Feeds / Careers / Accessibility / Feedback / Privacy & Policy / Legal Notices
Copyright© 1999-2012 Juniper Networks, Inc. All rights reserved.
Help
|
My Account
|
Log Out