You can install either zero Switch Fabric (SF) modules or one SF module in an EX8208 switch depending on the switch configuration you want to have. One SF module is included in the base configuration. See EX8208 Switch Configurations.
The SF module can be installed only in the slot labeled SF. The SF module is keyed so that it does not fit in any other slot in the chassis.
![]() | Note: Do not lift the SF module by holding the ejector levers. The levers cannot support the weight of the module. Lifting the module by the levers might bend the levers. Bent levers prevent the SF module from being properly seated in the chassis. |
Before you begin installing an SF module in an EX8208 switch:
Ensure that you have the following parts and tools available to install an SF module:
To install an SF module (see Figure 1):
If the ST LED is unlit, check whether there are enough power supplies installed. See Calculating Power Requirements for an EX8208 Switch. If more power supplies are needed, install additional power supplies. See Installing an AC Power Supply in an EX8200 Switch. If there are enough power supplies in the switch, remove and install the SF module again. See Removing an SF Module from an EX8208 Switch.
If the ST LED or the SF LED is lit steady yellow, the SF module has failed. Remove the SF module and install a new one. See Removing an SF Module from an EX8208 Switch.
Figure 1: Installing an SF Module in an EX8208 Switch