Installing a JCS1200 Fan Shuttle
Figure 1 shows how
to remove and install a fan shuttle.
Figure 1: Removing and Installing
a JCS1200 Fan Shuttle
- Attach an electrostatic discharge (ESD) grounding strap
to your bare wrist, and connect the strap to one of the ESD points
on the chassis.
- Make sure that no modules are installed
in the fan shuttle and that the release handles on the shuttle are
in the open position.
 | Caution:
Use your hands to hold the frame of the fan shuttle
where the fan module bays are located. Do not use the release handles
to hold the fan shuttle. |
- Orient the fan shuttle so that fan module bays
1 and 3 are above fan module bays 2 and 4.
- Align the shuttle with the chassis, and push the
shuttle into the chassis until it stops.
- Push the release handles to the closed position.
The shuttle moves back fully into the chassis.
- Tighten the four captive thumbscrews on the fan
shuttle.
- Tighten the captive thumbscrew on each release
handle.
 | Caution:
The release handles have a safety switch that disables
power output from the power boxes. If the release handles are not
secured to the chassis with the thumbscrews, the platform will not
power on. |
- Install any of the following modules that you removed
from the rear of the platform:
- Reconnect any cables that you disconnected
from the modules in the rear of the platform.
- Reconnect the power to the platform (see Connecting the JCS1200 AC Platform to AC Power or Connecting the JCS1200 DC Platform to DC Power).
- Restart any Routing Engines that were powered off
in the platform.