Home > Support > Technical Documentation > QFX Series > QFX3000 Hardware Documentation > Rack Requirements for a QFX3100 Director Device
Print
Rate and give feedback:  Feedback Received. Thank You!
Rate and give feedback: 
Close
This document helped resolve my issue.  Yes No

Additional Comments

800 characters remaining

May we contact you if necessary?

Name:  
E-mail: 
Submitting...
 

Related Documentation

  • EX Series
  • Rack-Mounting and Cabinet-Mounting Warnings
  • QFX Series
  • Chassis Physical Specifications for a QFX3100 Director Device
  • Cabinet Requirements for a QFX3100 Director Device
  • Rack-Mounting and Cabinet-Mounting Warnings
  • Mounting a QFX3100 Director Device on Four Posts in a Rack or Cabinet
  • Mounting a QFX3100 Director Device on Two Posts in a Rack or Cabinet
 

Rack Requirements for a QFX3100 Director Device

You can mount the QFX3100 Director device on two-post racks or four-post racks.

Rack requirements consist of:

  • Rack type
  • Mounting bracket hole spacing
  • Rack size and strength
  • Rack connection to the building structure

Table 1 provides the rack requirements and specifications for the QFX3100 Director device.

Table 1: Rack Requirements and Specifications for the QFX3100 Director Device

Rack Requirement

Guidelines

Rack type

Use a two-post rack or a four-post rack. You can mount the switch on any two-post or four-post rack that provides bracket holes or hole patterns spaced at 1 U (1.75 in. or 4.45 cm) increments and that meets the size and strength requirements to support the weight.

A U is the standard rack unit defined in Cabinets, Racks, Panels, and Associated Equipment (document number EIA-310-D) published by the Electronics Industry Association.

The rack must meet the strength requirements to support the weight of the chassis.

Mounting bracket hole spacing

The holes in the mounting brackets are spaced at 1 U (1.75 in. or 4.45 cm), so that the QFX3100 Director device can be mounted in any rack that provides holes spaced at that distance.

Rack size and strength

  • Ensure that the rack complies with one of these standards:
    • A 19-in. rack as defined in Cabinets, Racks, Panels, and Associated Equipment (document number EIA-310-D) published by the Electronics Industry Association.
    • A 600-mm rack as defined in the four-part Equipment Engineering (EE); European telecommunications standard for equipment practice (document numbers ETS 300 119-1 through 119-4) published by the European Telecommunications Standards Institute (http://www.etsi.org).

      The horizontal spacing between the rails in a rack that complies with this standard is usually wider than the QFX3100 Director device’s mounting brackets, which measure 19 in. (48.2 cm) from outer edge to outer edge. Use approved wing devices to narrow the opening between the rails as required.

  • Ensure that the rack is one of the following standard lengths:
    • 23.62 in. (600 mm)
    • 30 in. (762 mm)
    • 21.5 in. (546 mm)
  • Ensure that the rack rails are spaced widely enough to accommodate the QFX3100 Director device chassis' external dimensions. The outer edges of the front-mounting brackets extend the width of the chassis to 19 in. (48.2 cm).
  • The rack must be strong enough to support the weight of the QFX3100 Director device.
  • Ensure that the spacing of rails and adjacent racks allows for the proper clearance around the QFX3100 Director device and rack.

Rack connection to building structure

  • Secure the rack to the building structure.
  • If earthquakes are a possibility in your geographical area, secure the rack to the floor.
  • Secure the rack to the ceiling brackets as well as wall or floor brackets for maximum stability.

One pair of mounting brackets for mounting the QFX3100 Director device on two or four posts of a rack is supplied with each QFX3100 Director device.

 

Related Documentation

  • EX Series
  • Rack-Mounting and Cabinet-Mounting Warnings
  • QFX Series
  • Chassis Physical Specifications for a QFX3100 Director Device
  • Cabinet Requirements for a QFX3100 Director Device
  • Rack-Mounting and Cabinet-Mounting Warnings
  • Mounting a QFX3100 Director Device on Four Posts in a Rack or Cabinet
  • Mounting a QFX3100 Director Device on Two Posts in a Rack or Cabinet
 

Published: 2012-03-23

 
  • About Juniper
  • The New Network
  • Investor Relations
  • Press Releases
  • Newsletters
  • Juniper Offices
  • Resources
  • How to Buy
  • Partner Locator
  • Image Library
  • Visio Templates
  • Security Center
  • Community
  • Forums
  • Blogs
  • Junos Central
  • Social Media
  • Support
  • Technical Documentation
  • Knowledge Base (KB)
  • Software Downloads
  • Product Licensing
  • Contact Support
Site Map / RSS Feeds / Careers / Accessibility / Feedback / Privacy & Policy / Legal Notices
Copyright© 1999-2012 Juniper Networks, Inc. All rights reserved.
Help
|
My Account
|
Log Out