MX240 Router Environmental Specifications
Table 1 specifies the
environmental specifications required for normal router operation.
In addition, the site should be as dust-free as possible.
Table 1: Routers Environmental Specifications
Description | Value |
|---|
Altitude | No performance degradation to 10,000 ft
(3048 m) |
Relative humidity | Normal operation ensured in relative humidity
range of 5% to 90%, noncondensing |
Temperature | Normal operation ensured in temperature range
of 32°F (0°C) to 104°F (40°C) Nonoperating storage temperature in shipping container: –40°F (–40°C)
to 158°F (70°C) |
Seismic | Designed to meet Telcordia Technologies Zone 4 earthquake requirements |
Maximum thermal output | AC power: 7161 BTU/hour (2100 W) DC power: 5074 BTU/hour (1488 W) |
 | Note:
Install the router only in restricted areas, such as dedicated
equipment rooms and equipment closets, in accordance with Articles
110-16, 110-17, and 110-18 of the National Electrical Code, ANSI/NFPA
70. |
Related Documentation
- JCS 1200
- General Safety Guidelines for M Series, MX Series, and T Series Routers
- General Safety Warnings for M Series, MX Series, and T Series Routers
- M Series
- General Safety Guidelines for M Series, MX Series, and T Series Routers
- General Safety Warnings for M Series, MX Series, and T Series Routers
- Compliance Statements for Environmental Requirements for M Series, MX Series, and T Series Routers
- MX Series
- Routine Maintenance Procedures for the MX240 Router
- General Safety Guidelines for M Series, MX Series, and T Series Routers
- General Safety Warnings for M Series, MX Series, and T Series Routers
- Compliance Statements for Environmental Requirements for M Series, MX Series, and T Series Routers
- T Series
- General Safety Guidelines for M Series, MX Series, and T Series Routers
- General Safety Warnings for M Series, MX Series, and T Series Routers
- Compliance Statements for Environmental Requirements for M Series, MX Series, and T Series Routers
Published: 2011-02-25