Home > Support > Technical Documentation > QFX Series > QFX3000 Hardware Documentation > Clearance Requirements for Airflow and Hardware Maintenance for a QFX3008-I Interconnect Device
Print
Rate and give feedback:  Feedback Received. Thank You!
Rate and give feedback: 
Close
This document helped resolve my issue.  Yes No

Additional Comments

800 characters remaining

May we contact you if necessary?

Name:  
E-mail: 
Submitting...
 

Related Documentation

  • EX Series
  • Rack-Mounting and Cabinet-Mounting Warnings
  • QFX Series
  • Cooling System and Airflow in a QFX3008-I Interconnect Device
  • Cabinet Requirements for a QFX3008-I Interconnect Device
  • Rack Requirements for a QFX3008-I Interconnect Device
  • Rack-Mounting and Cabinet-Mounting Warnings
 

Clearance Requirements for Airflow and Hardware Maintenance for a QFX3008-I Interconnect Device

When planning the site for installing a QFX3008-I Interconnect device, you must allow sufficient clearance around the device.

Follow these clearance requirements:

  • For the cooling system to function properly, the airflow around the chassis must be unrestricted. Do not block the air intake or exhaust areas shown in Figure 1 and Figure 2.

    The air intake to cool the front card cage and powerhouse is located below the front fan tray on the chassis. Hot air exhausts from the powerhouse at the bottom of the chassis, and above the rear fan tray at the top of the chassis.

    Figure 1: Airflow Through the Front Card Cage and Powerhouse

    Airflow Through
the Front Card Cage and Powerhouse

    The air intake to cool the rear card cage is located on the front sides of the chassis. Cool air is pulled in through the side fan trays. Hot air exhausts from the Control Boards and rear cards.

    Figure 2: Airflow Through the Rear Card Cage

    Airflow Through
the Rear Card Cage
  • If you are mounting the device on a rack or cabinet along with other equipment, ensure that the exhaust from other equipment does not blow into the intake vents of the chassis.
  • Leave at least 24 in. (61 cm) both in front of and behind the switch. Allow at least 6 in. (15.2 cm) of clearance on each side of the chassis. Leave adequate space at the front of the switch for service personnel to remove and install hardware components. NEBS GR-63 recommends that you allow at least 30 in. (76.2 cm) in front of the rack or cabinet and 24 in. (61 cm) behind the rack or cabinet. See Figure 3.

    Figure 3: Clearance Requirements for Airflow and Hardware Maintenance for a QFX3008-I Interconnect Device

     Clearance Requirements for Airflow and Hardware Maintenance for
a QFX3008-I Interconnect Device
 

Related Documentation

  • EX Series
  • Rack-Mounting and Cabinet-Mounting Warnings
  • QFX Series
  • Cooling System and Airflow in a QFX3008-I Interconnect Device
  • Cabinet Requirements for a QFX3008-I Interconnect Device
  • Rack Requirements for a QFX3008-I Interconnect Device
  • Rack-Mounting and Cabinet-Mounting Warnings
 

Published: 2012-03-23

 
  • About Juniper
  • The New Network
  • Investor Relations
  • Press Releases
  • Newsletters
  • Juniper Offices
  • Resources
  • How to Buy
  • Partner Locator
  • Image Library
  • Visio Templates
  • Security Center
  • Community
  • Forums
  • Blogs
  • Junos Central
  • Social Media
  • Support
  • Technical Documentation
  • Knowledge Base (KB)
  • Software Downloads
  • Product Licensing
  • Contact Support
Site Map / RSS Feeds / Careers / Accessibility / Feedback / Privacy & Policy / Legal Notices
Copyright© 1999-2012 Juniper Networks, Inc. All rights reserved.
Help
|
My Account
|
Log Out