Home > Support > Technical Documentation > M Series Routers > M120 Router Hardware > M120 Rack Mounting Requirements
Print
Rate and give feedback:  Feedback Received. Thank You!
Rate and give feedback: 
Close
This document helped resolve my issue.  Yes No

Additional Comments

800 characters remaining

May we contact you if necessary?

Name:  
E-mail: 
Submitting...

M Series Search

Advanced Search |  Search Tips
 

Supported Platforms

  • M120 Routers
 
 

Related Documentation

  • JCS 1200
  • Installation Safety Warnings for M Series, MX Series, and T Series Routers
  • M Series
  • M120 Clearance Requirements for Airflow and Hardware Maintenance
  • Installing the Mounting Hardware for a Center-Mount Open-Frame Rack
  • Installing the Mounting Hardware for a Front-Mount Four-Post Rack or Cabinet
  • Installing the Mounting Hardware for a Front-Mount Open-Frame Rack
  • Installation Safety Warnings for M Series, MX Series, and T Series Routers
  • Installing the M120 Router Without Using a Mechanical Lift
  • MX Series
  • Installation Safety Warnings for M Series, MX Series, and T Series Routers
  • T Series
  • Installation Safety Warnings for M Series, MX Series, and T Series Routers
 
Recent Community Posts
Show All Show Fewer 
 
 
Related Links
M Series Product Literature
  • Junos Central
  • Junos Technotes
  • Junos Day One Books
M Series Certification
  • Fast Track Certification Program
  • Certification Study Guides
Junos Technical Education Courses (Free)
  • Networking Fundamentals
  • Junos As A Second Language
  • Junos As A Scripting Language
  • Junos As A Security Language
  • Juniper Networks Books
Support
  • Junos Software (Canada & US)  Login required
  • Junos Software (Worldwide) Login required
  • Knowledge Base - Browse M Series Articles  Login required
  • Technical Bulletins for M Series Login required
  • IOS to Junos Migration Tool Login required
  • ScreenOS to Junos software with enhanced services Migration Tool Login required
Show All Show Fewer 
 
 

M120 Rack Mounting Requirements

The router can be installed in a rack. Many types of racks are acceptable, including four-post (telco) racks and open-frame racks. An example of an open-frame rack appears in Figure 1. Table 1 summarizes rack requirements and specifications for the M120 router.

Table 1: M120 Rack Requirements and Specifications

Rack Requirement

Guidelines

Rack type and mounting bracket hole spacing

Use a four-post rack or a two-post rack. You can mount the router on any four-post or two-post rack that provides bracket holes or hole patterns spaced at 1 U (1.75-in./4.44-cm) increments and that meets the size and strength requirements specified in this table.

A U is the standard rack unit defined in Cabinets, Racks, Panels, and Associated Equipment (document number EIA-310–D) published by the Electronics Industry Association (http://www.eia.org).

Rack size and strength

  • Ensure that the rack is a 19-in. rack as defined in Cabinets, Racks, Panels, and Associated Equipment (document number EIA-310–D) published by the Electronics Industry Association (http://www.eia.org).
  • Ensure that the rack is one of the following standard lengths:
    • 23.62 in. (600 mm)
    • 30.0 in. (762 mm)
    • 21.5 in. (800 mm)
  • The rack rails must be spaced widely enough to accommodate the router chassis's external dimensions: 20.75 in. (52.71 cm) high, 24.3 in. (61.7 cm) deep, and 17.43 in. (44.3 cm) wide. The outer edges of the mounting brackets extend the width to 19 in. (48.3 cm). The spacing of rails and adjacent racks must also allow for the clearances around the router and rack that are specified in M120 Clearance Requirements for Airflow and Hardware Maintenance.
  • All mounting options require you to install the supplied large mounting shelf. The supplied small mounting shelf is needed for a front-mount four-post rack or cabinet.
  • If a front-mount rack is used, you must support the back of the router with the large mounting shelf included with your shipment, or some other structure.
  • For a front-mount rack, you use the front-mounting flanges on the front of the chassis instead of the mounting brackets. The flanges have holes for rack-mounting screws, spaced at 3.5 in. (8.89 cm). In addition, if you are mounting the router in a four-post rack or cabinet, you must install the spacer bars on the rack before you mount the chassis. For instructions about installing the mounting hardware, see Installing the Mounting Hardware for a Front-Mount Four-Post Rack or Cabinet, Installing the Mounting Hardware for a Front-Mount Open-Frame Rack, or Installing the Mounting Hardware for a Center-Mount Open-Frame Rack.
  • The chassis height of 20.75 in. (52.71 cm) is approximately 12 U. A U is the standard rack unit defined in Cabinets, Racks, Panels, and Associated Equipment (document number EIA-310-D) published by the Electronics Industry Association. You can stack four M120 routers in a rack that has at least 48 U (84 in. or 2.1 m) of usable vertical space.
  • The rack must be strong enough to support the weight of the fully configured router, up to 225 lb (102.1 kg). If you stack four fully configured routers in one rack, it must be capable of supporting about 900 lb (408.4 kg).
  • Ensure that the spacing of rails and adjacent racks allows for the proper clearance around the switch and rack as specified in M120 Clearance Requirements for Airflow and Hardware Maintenance.

Rack connection to the building structure

  • Secure the rack to the building structure.
  • If earthquakes are a possibility in your geographical area, secure the rack to the floor.
  • Secure the rack to the ceiling brackets as well as wall or floor brackets for maximum stability.

Figure 1: Typical Open-Frame Rack

Image g001011.gif
 

Related Documentation

  • JCS 1200
  • Installation Safety Warnings for M Series, MX Series, and T Series Routers
  • M Series
  • M120 Clearance Requirements for Airflow and Hardware Maintenance
  • Installing the Mounting Hardware for a Center-Mount Open-Frame Rack
  • Installing the Mounting Hardware for a Front-Mount Four-Post Rack or Cabinet
  • Installing the Mounting Hardware for a Front-Mount Open-Frame Rack
  • Installation Safety Warnings for M Series, MX Series, and T Series Routers
  • Installing the M120 Router Without Using a Mechanical Lift
  • MX Series
  • Installation Safety Warnings for M Series, MX Series, and T Series Routers
  • T Series
  • Installation Safety Warnings for M Series, MX Series, and T Series Routers
 

Published: 2011-02-23

 
  • About Juniper
  • The New Network
  • Investor Relations
  • Press Releases
  • Newsletters
  • Juniper Offices
  • Resources
  • How to Buy
  • Partner Locator
  • Image Library
  • Visio Templates
  • Security Center
  • Community
  • Forums
  • Blogs
  • Junos Central
  • Social Media
  • Support
  • Technical Documentation
  • Knowledge Base (KB)
  • Software Downloads
  • Product Licensing
  • Contact Support
Site Map / RSS Feeds / Careers / Accessibility / Feedback / Privacy & Policy / Legal Notices
Copyright© 1999-2012 Juniper Networks, Inc. All rights reserved.
Help
|
My Account
|
Log Out