Juniper Networks
Log in
|
How to Buy
|
Contact Us
|
United States (Change)
Choose Country
Close

Choose Country

North America

  • United States

Europe

  • Deutschland - Germany
  • España - Spain
  • France
  • Italia - Italy
  • Россия - Russia
  • United Kingdom

Asia Pacific

  • Asean Region (Vietnam, Indonesia, Singapore, Malaysia)
  • Australia
  • 中国 - China
  • India
  • 日本 - Japan
  • 대한민국 - Korea
  • 台灣 - Taiwan
Solutions
Products & Services
Company
Partners
Support
Education
Community
Security Intelligence Center

Technical Documentation

Download Software
Research a Problem Login required
Case Management Login required
Contract & Product Management Login required
Technical Documentation
Documentation Archive
Enterprise MIBs
File Format Help
Glossary
Portable Libraries
End-of-Life Products
Contact Support
Guidelines and Policies
Security Resources
Home > Support > Technical Documentation > EX Series > EX8208 Hardware Documentation > Rack Requirements for an EX8208 Switch
Print
Rate and give feedback:  Feedback Received. Thank You!
Rate and give feedback: 
Close
This document helped resolve my issue.  Yes No

Additional Comments

800 characters remaining

May we contact you if necessary?

Name:  
E-mail: 
Submitting...
 

Related Documentation

  • EX Series
  • Rack-Mounting and Cabinet-Mounting Warnings
  • Cabinet Requirements and Specifications for an EX8208 Switch
  • Chassis Physical Specifications of an EX8208 Switch
  • QFX Series
  • Rack-Mounting and Cabinet-Mounting Warnings
 

Rack Requirements for an EX8208 Switch

You can mount EX8208 switches on four-post racks or two-post racks. See Figure 1 and Figure 2.

Rack requirements consist of:

  • Rack type
  • Mounting bracket hole spacing
  • Rack size and strength
  • Rack connection to the building structure

Table 1 summarizes rack requirements and specifications for EX8208 switches.

Figure 1 shows four-post rack installation. Figure 2 shows two-post rack installation.

Note: To manage airflow in a hot-aisle-cold-aisle data center setup, you might want to use the customized rack solution for EX8200 switches offered by Chatsworth Products, Inc.

Table 1: Rack Requirements and Specifications for an EX8208 Switch

Rack Requirement

Guidelines

Rack type and mounting bracket hole spacing

Use a four-post rack or a two-post rack. You can mount the switch on any four-post or two-post rack that provides bracket holes or hole patterns spaced at 1 U (1.75 in./4.44 cm) increments and that meets the size and strength requirements specified in this table.

A U is the standard rack unit defined in Cabinets, Racks, Panels, and Associated Equipment (document number EIA-310–D) published by the Electronics Industry Association (http://www.eia.org).

You can stack three EX8208 switches in a four-post rack that has at least 42 U; if you install the optional power cord tray, a minimum of 45 U are required. You can stack three EX8208 switches in a two-post rack that has 45 U (installing the power cord tray is mandatory for two-post rack installations). In all cases, the rack must meet the strength requirements to support the weight.

Rack size and strength

  • Ensure that the rack is a 19-in. rack as defined in Cabinets, Racks, Panels, and Associated Equipment (document number EIA-310–D) published by the Electronics Industry Association (http://www.eia.org).
  • Ensure that the rack is one of the following standard lengths:
    • 23.62 in. (600 mm)
    • 30.0 in. (762 mm)
    • 21.5 in. (546 mm)
  • Ensure that the rack rails are spaced widely enough to accommodate the EX8208 switch chassis' external dimensions of 24.25 in. (61.6 cm) height, 17.25 in. (43.815 cm) width, 20 in. (50.8 cm) depth. The outer edges of the front-mounting brackets extend the width to 19 in. (48.3 cm).
  • The EX8208 switch chassis height of 24.25 in. (61.6 cm) is approximately 14 U. If you install the power cord tray (optional for four-post rack installations, mandatory for two-post rack installations), the chassis and power cord tray consume 15 U.
  • The rack must be strong enough to support the weight of the fully loaded switch. A fully loaded EX8208 switch weighs up to 284 lb (130 kg). If you stack three fully loaded EX8208 switches in one rack, that rack must support up to 852 lb (386 kg).
  • Ensure that the spacing of rails and adjacent racks allows for the proper clearance around the switch and rack as specified in Clearance Requirements for Airflow and Hardware Maintenance for an EX8208 Switch.

Rack connection to the building structure

  • Secure the rack to the building structure.
  • If earthquakes are a possibility in your geographical area, secure the rack to the floor.
  • Secure the rack to the ceiling brackets as well as wall or floor brackets for maximum stability.

Figure 1: Installing an EX8208 Switch in a Four-Post Rack

Installing an
EX8208 Switch in a Four-Post Rack

Figure 2: Installing an EX8208 Switch in a Two-Post Rack

Installing an
EX8208 Switch in a Two-Post Rack
 

Related Documentation

  • EX Series
  • Rack-Mounting and Cabinet-Mounting Warnings
  • Cabinet Requirements and Specifications for an EX8208 Switch
  • Chassis Physical Specifications of an EX8208 Switch
  • QFX Series
  • Rack-Mounting and Cabinet-Mounting Warnings
 

Published: 2011-11-01

 
  • About Juniper
  • The New Network
  • Investor Relations
  • Press Releases
  • Newsletters
  • Juniper Offices
  • Resources
  • How to Buy
  • Partner Locator
  • Image Library
  • Visio Templates
  • Security Center
  • Community
  • Forums
  • Blogs
  • Junos Central
  • Social Media
  • Support
  • Technical Documentation
  • Knowledge Base (KB)
  • Software Downloads
  • Product Licensing
  • Contact Support
Site Map / RSS Feeds / Careers / Accessibility / Feedback / Privacy & Policy / Legal Notices
Copyright© 1999-2012 Juniper Networks, Inc. All rights reserved.
Help
|
My Account
|
Log Out